INTRODUCTION
This project analyses the heat island effect in a data centre with an IT power rating of approximately 65 MW under various expected climate scenarios agreed with the client in accordance with the European Energy Efficiency Directive. To this end, simulation models based on Computational Fluid Dynamics (CFD) are used.
The main objective is to ensure that the data centre’s operations do not significantly raise the temperature of the urban environment or neighbouring areas, in accordance with regulations.
This phenomenon has been studied within a radius of approximately 1 km in order to obtain the data required for the relevant environmental study and to analyse the spread of hot air and its dilution in the atmosphere.
CFD MODEL
Firstly, the geometry required for the thermal study was generated from the plans and data relating to the position, orientation and layout of the cooling units, power generators and other components within the data centre. This geometric modelling approach enables us to efficiently analyse both the airflow and the temperature field by reducing the mesh size requirements in regions of low interest.
For this project, models were developed in ScStream that were capable of reproducing the expected behaviour.
The modelling has taken into account the supply and exhaust air temperatures, as well as the size of the air intakes and the airflow absorbed by the chillers; furthermore, assumptions have been made regarding the heat emitted by both the buildings and the road surface in order to realistically assess the dispersion and recirculation of air in the surrounding environment.
STUDY USING CFD SIMULATION
Once the models have been defined, the various case studies can be calculated by numerically solving the equations that describe the motion of the air and the temperature field for an incompressible turbulent flow. We first assess the convergence criteria by monitoring the residuals and the stability of the parameters under investigation, particularly the residuals and the velocities. Once the models have finished running, we proceed to obtain results during the post-processing stage.
The aim of the case studies was to verify that suitable thermal conditions were maintained in the various scenarios. To this end, temperature and velocity maps are provided for various representative cross-sections, along with flow lines and thermal gradients within the buildings and surrounding areas within the data centre’s sphere of influence.
The following images are displayed:
- The velocity of the plumes of hot gas associated with a specified temperature.
- The thermal impact at a height of 1.5 m above ground level, with the horizontal plane taken as a reference for assessing the thermal exposure perceived by a person of average height.
- The velocity map in that reference frame.